Circuit Breakers

    Inventory #

  AB0555

DSL-206

by

Square D

Air Circuit Breaker

800 amps

600 volts

Low Voltage

all specifications...
  • DSL-206 available as-is,
    or remanufactured
  • Remanufactured breaker includes
    1 Year Parts & Labor Warranty
  • Large stock of DSL-206 Replacement Parts
Product Photos
076 077 078 079 080

Current Condition

This photo shows a similar circuit breaker to AB0555, after it had undergone remanufacturing by
West Coast Switchgear. Actual photos of this DSL-206 Air Breaker in its current condition are shown above.

Detailed Specs
General Specifications

Catalog #: DSL-206

Type: Air Breaker

Manufacturer: Square D


Ratings

Frame Current: 800 amps

Voltage: 600 volts

Manual operation

Drawout mounting


Trip Unit

Type: Amptector

Manufacturer: Westinghouse

Trip Function: LSI


Written Detailed Specification

Square D DSL-206 Drawout mounted Air Circuit Breaker, Low Voltage, 800 Amps, 600 Volts, Manual operation.


Warranty

West Coast Switchgear warranties this reconditioned Square D DSL-206 circuit breaker for one year, including all labor, freight and materials required to return it to operational standards. West Coast Switchgear guarantees this breaker will operate to your satisfaction given competent supervision and normal load and usage conditions. Any repairs performed without the express written permission of West Coast Switchgear Inc. shall invalidate this warranty. West Coast Switchgear shall not be liable to the customer, or to any other person, for consequential damages, lost profits or other kinds of damages arising out of the sale or use of this circuit breaker.


The Square D DSL-206 from West Coast Switchgear

All Square D DSL-206 Air Breakers can be purchased as remanufactured to factory standards (please see DSL-206 factory remanufacturing specification). You can also order your Square D DSL-206 Air Breaker wired to your specified wiring diagrams. We also carry a large stock of replacement parts for the Square D DSL-206 Air Breaker. Call one of our sales consultants today.

Remanufacturing
Circuit Breaker Remanufacturing
Circuit Breaker Remanufacturing

At West Coast Switchgear, we don’t just rebuild Air Breakers, we remanufacture them. All of our remanufactured circuit breakers conform to NETA and ANSI C37 specifications, and all tolerances are checked to meet or exceed the original manufacturer’s specifications. Here’s how we will remanufacture this Square D DSL-206 for you:

Inspection and Initial Testing

We’ll start with an initial inspection and test of this Air Breaker. We first want to check its mechanical and electrical operation. We’ll then perform a “Ductor” test, a “Megger” test, and several other tests to determine our starting point. (See “Testing Procedures” below for further description.)

During our initial testing, we’ll take note of any wiring, taping, or heat shrinking that shows any signs of deterioration. We’ll also note any springs showing signs of distortion, rust, brittleness, or improper compression. Noted items will be replaced later using equivalent or superior components.

Disassembly, Cleaning, and Replacement

All of our remanufactured circuit breakers are dismantled down to the last moving part:

  • Conductive parts are bead blasted as needed and cleaned using a vibratory cleaner.
  • Plated parts showing signs of peeling are replated or replaced.
  • Insulated parts and pole pieces are solvent cleaned to be free of silicone, oil, paint and moisture.
  • Frame parts and mechanism parts are aluminum oxide blasted and then repainted or replated.
  • All standard hardware is replaced with new hardware.
  • All pins are replated.
  • Roller and needle bearings are lubricated. (Nylon sleeve bearings do not require lubrication).
  • All springs are either replated or replaced.
  • Control wiring is cleaned or replaced as necessary.
  • Toggle switches, motor cut-off switches and relays are cleaned or replaced with identical or equivalent devices. Voltage and amperage ratings will always meet or exceed original specifications.

Reassembly and Final Testing

Now that the circuit breaker has been torn down with all of its components cleaned, refurbished or replaced, it’s time to put it all back together. West Coast Switchgear follows a meticulous quality control procedure during reassembly to ensure years of trouble-free operation. Breakers are reassembled to the original factory specification as follows:

Circuit Breaker Remanufacturing
  • Frame parts are reassembled and aligned.
  • Contact assemblies are adjusted to the manufacture's guidelines.
  • Current-carrying parts are reassembled and torqued to the manufacturer's or NETA standards.
  • New retainer pins or clips are carefully installed and checked.
  • Electrical devices and wiring harness are re-installed on the breaker and checked per factory or customer's wiring specifications.

Upon completion of reassembly, the now completely remanufactured circuit breaker is retested and certified by a quality control engineer. The rebuilt circuit breaker will be delivered to you with a Job Packet containing an Initial Inspection Report, a Quality Control Checklist, and a Final Test Report. These reports include all pertinent information to ensure that you are receiving a product of the highest quality.


Testing Procedures

"Ductor" Test

The Digital Low Resistance Ohmmeter (“Ductor”) uses dual spike probes to measure the resistance of the current carrying path of the entire phase. This test includes as much of the path as practical for each pole, ensuring that the entire pole (not just the contacts) has a low resistance.

“Megger” Test

The insulation of the circuit breaker is tested utilizing a 1000 volt megohmmeter (“Megger”). The breaker is tested in the closed position because of the additional stress placed on the insulators due to spring tension. The insulation is tested between phase-to-phase and phase-to-ground. With the breaker open, the breaker is tested from line-side to load-side of each pole, verifying insulation between the source and the load. The lowest reading of each phase is recorded. West Coast Switchgear maintains a standard requirement of a minimum of 500 megohms, ten times NETA minimum requirement.

High Current Primary Injection Test

The high current test is performed using a low voltage (usually less than 12 VAC) high current test set. Each phase or pole is tested for every trip function provided on the trip unit. The test is conducted in the following order to standardize results:

  • Long time (300% of pick-up current)
  • Short time (150% of pick-up current)
  • Ground time (150% of pick-up current)
  • Instantaneous1 (Determines the pick-up current)

1 Instantaneous is not a time test like the others. Therefore the test uses a short pulse of current and the short time functions are overridden or adjusted out of range of the instantaneous setting.

Control Circuitry Test

The control diagram of the circuit breaker is verified against your drawing or the manufacturer’s diagram. The circuit breaker is electrically operated using a variable power supply to check the pick-up voltage of the trip coil, under-voltage coil, and the closing coil. The maximum voltage limit of the close coil is also tested so it will still close and latch.


Warranty

West Coast Switchgear warranties this refurbished Square D DSL-206 circuit breaker for one year, including all labor, freight and materials required to return it to operational standards. West Coast Switchgear guarantees this breaker will operate to your satisfaction given competent supervision and normal load and usage conditions. Any repairs performed without the express written permission of West Coast Switchgear Inc. shall invalidate this warranty. West Coast Switchgear shall not be liable to the customer, or to any other person, for consequential damages, lost profits or other kinds of damages arising out of the sale or use of this circuit breaker.

Other Products
Similar Products to AB0555 (DSL-206)
Catalog Number Manufacturer Type Frame Current Voltage
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 Square D Air Breaker 800 amps 600 volts
DSL-206 General Electric Air Breaker 800 amps 600 volts
DSL-206 Westinghouse Air Breaker 800 amps 600 volts
DSL-206 Westinghouse Air Breaker 800 amps 600 volts
DSL-206 Westinghouse Air Breaker 800 amps 600 volts
DSL-206 Westinghouse Air Breaker 800 amps 600 volts
DSL-206 Westinghouse Air Breaker 800 amps 600 volts
DSL-206 Westinghouse Air Breaker 800 amps 600 volts